Water resources industry
Release time:
22-09-08
Source:
1.1 Application Characteristics
Load types: drainage pumps, sewage pumps, etc.
Motor power: The motor power of municipal rainwater drainage pumps is within 1000kW, and the motor power of water conservancy drainage and sewage treatment plant pumps is within 2000kW.
Grid situation: For those using urban power supply (e.g., municipal rainwater drainage pumps, water conservancy drainage pumps), the grid capacity is relatively small, and the quality requirements for the grid are high. Due to the low power factor during motor operation, it is generally configured with one motor and one reactive power compensation device to improve the input power factor of the motor.
Special requirements: For municipal and water conservancy drainage projects, land costs are relatively high. To save project costs, in recent years, the three-in-one thyristor soft starter device (i.e., a combination of power switch cabinet and soft starter device) has been widely used. The three-in-one high-voltage soft starter device has high integration and small size, which is favored by users.
Soft start control mode: Current limiting mode is used more frequently.
Shutdown control mode: Instant stop method. This type of pump has a low lift and will not produce a 'water hammer effect'. Except for special user requirements, there is no need to use the soft stop function during shutdown.
Soft start cabinet form: Currently, the three-in-one high-voltage soft starter device is used more frequently, with the cabinet type being: KYN28-12A.
Water conservancy promotion certificate:

1.2 Schematic diagram of the three-in-one high-voltage soft starter device (taking the 10kV one-to-one control method as an example)

Note: This diagram includes 6 three-in-one high-voltage soft starter devices.